aptomat là gì

Circuit Breaker

A two-pole miniature circuit breaker

Electronic symbol
An air circuit breaker for low-voltage (less kêu ca 1,000 volt) power distribution switchgear
Four one-pole miniature circuit breakers

A circuit breaker is an electrical safety device designed đồ sộ protect an electrical circuit from damage caused by overcurrent. Its basic function is đồ sộ interrupt current flow đồ sộ protect equipment and đồ sộ prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) đồ sộ resume normal operation.

Bạn đang xem: aptomat là gì

Circuit breakers are made in varying sizes, from small devices that protect low-current circuits or individual household appliances, đồ sộ large switchgear designed đồ sộ protect high voltage circuits feeding an entire thành phố. The generic function of a circuit breaker, or fuse, as an automatic means of removing power from a faulty system, is often abbreviated as OCPD (Over Current Protection Device).

Origins[edit]

An early size of circuit breaker was described by Thomas Edison in an 1879 patent application, although his commercial power distribution system used fuses.[1] Its purpose was đồ sộ protect lighting circuit wiring from accidental short circuits and overloads. A modern miniature circuit breaker similar đồ sộ the ones now in use was patented by Brown, Boveri & Cie in 1924. Hugo Stotz, an engineer who had sold his company đồ sộ Đài truyền hình BBC, was credited as the inventor on DRP (Deutsches Reichspatent) 458392.[2] Stotz's invention was the forerunner of the modern thermal-magnetic breaker commonly used in household load centers đồ sộ this day.

Interconnection of multiple generator sources into an electrical grid required the development of circuit breakers with increasing voltage ratings and increased ability đồ sộ safely interrupt the increasing short-circuit currents produced by networks. Simple air-break manual switches produced hazardous arcs when interrupting high voltages; these gave way đồ sộ oil-enclosed contacts, and various forms using the directed flow of pressurized air, or pressurized oil, đồ sộ cool and interrupt the arc. By 1935, the specially constructed circuit breakers used at the Boulder Dam project used eight series breaks and pressurized oil flow đồ sộ interrupt faults of up đồ sộ 2,500 MVA, in three cycles of the AC power frequency.[3]

Operation[edit]

All circuit breaker systems have common features in their operation, but details vary substantially depending on the voltage class, current rating and type of the circuit breaker.

The circuit breaker must first detect a fault condition. In small mains and low voltage circuit breakers, this is usually done within the device itself. Typically, the heating or magnetic effects of electric current are employed. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices đồ sộ sense a fault condition and đồ sộ operate the opening mechanism. These typically require a separate power source, such as a battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays, and an internal control power source.

Once a fault is detected, the circuit breaker contacts must open đồ sộ interrupt the circuit; this is commonly done using mechanically stored energy contained within the breaker, such as a spring or compressed air đồ sộ separate the contacts. Circuit breakers may also use the higher current caused by the fault đồ sộ separate the contacts, such as thermal expansion or a magnetic field. Small circuit breakers typically have a manual control lever đồ sộ switch off the load or reset a tripped breaker, while larger units use solenoids đồ sộ trip the mechanism, and electric motors đồ sộ restore energy đồ sộ the springs.

The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of tương tác material due đồ sộ arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts.

When a high current or voltage is interrupted, an arc is generated. The length of the arc is generally proportional đồ sộ the voltage while the intensity (or heat) is proportional đồ sộ the current. This arc must be contained, cooled and extinguished in a controlled way, ví that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas, or oil as the medium the arc forms in. Different techniques are used đồ sộ extinguish the arc including:

  • Lengthening or deflecting the arc
  • Intensive cooling (in jet chambers)
  • Division into partial arcs
  • Zero point quenching (contacts open at the zero current time crossing of the AC waveform, effectively breaking no load current at the time of opening. The zero-crossing occurs at twice the line frequency; i.e., 100 times per second for 50 Hz and 120 times per second for 60 Hz AC.)
  • Connecting capacitors in parallel with contacts in DC circuits.

Finally, once the fault condition has been cleared, the contacts must again be closed đồ sộ restore power đồ sộ the interrupted circuit.

Arc interruption[edit]

Low-voltage miniature circuit breakers (MCB) use air alone đồ sộ extinguish the arc. These circuit breakers contain so-called arc chutes, a stack of mutually insulated parallel metal plates that divide and cool the arc. By splitting the arc into smaller arcs the arc is cooled down while the arc voltage is increased and serves as an additional impedance that limits the current through the circuit breaker. The current-carrying parts near the contacts provide easy deflection of the arc into the arc chutes by a magnetic force of a current path, although magnetic blowout coils or permanent magnets could also deflect the arc into the arc chute (used on circuit breakers for higher ratings). The number of plates in the arc chute is dependent on the short-circuit rating and nominal voltage of the circuit breaker.

In larger ratings, oil circuit breakers rely upon vaporization of some of the oil đồ sộ blast a jet of oil through the arc.[4]

Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6) đồ sộ quench the stretched arc.

Vacuum circuit breakers have minimal arcing (as there is nothing đồ sộ ionize other kêu ca the tương tác material). The arc quenches when it is stretched a very small amount (less kêu ca 2–3 mm (0.08–0.1 in)). Vacuum circuit breakers are frequently used in modern medium-voltage switch gear đồ sộ 38,000 volts.

Air circuit breakers may use compressed air đồ sộ blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc.

Circuit breakers are usually able đồ sộ terminate all current very quickly: typically the arc is extinguished between 30 ms and 150 ms after the mechanism has been tripped, depending upon age and construction of the device. The maximum current value and let-through energy determine the quality of the circuit breakers.

Short circuit[edit]

Circuit breakers are rated both by the normal current that they are expected đồ sộ carry, and the maximum short-circuit current that they can safely interrupt. This latter figure is the ampere interrupting capacity (AIC) of the breaker.

Under short-circuit conditions, the calculated or measured maximum prospective short-circuit current may be many times the normal, rated current of the circuit. When electrical contacts open đồ sộ interrupt a large current, there is a tendency for an arc đồ sộ size between the opened contacts, which would allow the current đồ sộ continue. This condition can create conductive ionized gases and molten or vaporized metal, which can cause the further continuation of the arc, or creation of additional short circuits, potentially resulting in the explosion of the circuit breaker and the equipment that it is installed in. Therefore, circuit breakers must incorporate various features đồ sộ divide and extinguish the arc.

The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher kêu ca the breaker's interrupting capacity rating may result in failure of the breaker đồ sộ safely interrupt a fault. In a worst-case scenario, the breaker may successfully interrupt the fault, only đồ sộ explode when reset.

Typical domestic panel circuit breakers are rated đồ sộ interrupt 6 kA (6000 A) short-circuit current.

Miniature circuit breakers used đồ sộ protect control circuits or small appliances may not have sufficient interrupting capacity đồ sộ use at a panel board; these circuit breakers are called "supplemental circuit protectors" đồ sộ distinguish them from distribution-type circuit breakers.

Standard current ratings[edit]

Time till trip versus current as multiple of nominal current

Circuit breakers are manufactured in standard sizes, using a system of preferred numbers đồ sộ cover a range of ratings. Miniature circuit breakers have a fixed trip setting; changing the operating current value requires changing the whole circuit breaker. Larger circuit breakers can have adjustable trip settings, allowing standardized elements đồ sộ be applied but with a setting intended đồ sộ improve protection. For example, a circuit breaker with a 400 ampere "frame size" might have its over current detection phối đồ sộ operate at only 300 amperes, đồ sộ protect a feeder cable.

For low voltage distribution circuit breakers, International Standards, IEC 60898-1 defines the rated current as the maximum current that the breaker is designed đồ sộ carry continuously. The commonly available preferred values for the rated current are 1 A, 2 A, 4 A, 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A,[5] and 125 A. The circuit breaker is labeled with the rated current in amperes prefixed by a letter, which indicates the instantaneous tripping current that causes the circuit breaker đồ sộ trip without intentional time delay expressed in multiples of the rated current:

Type Instantaneous tripping current
B 3-5 times rated current In For example a 10 A device will trip at 30–50 A
C 5 đồ sộ 10 times In
D 10-20 times In
K 8 đồ sộ 12 times In

For the protection of loads that cause frequent short duration (approximately 400 ms đồ sộ 2 s) current peaks in normal operation.

Z 2 đồ sộ 3 times In for periods in the order of tens of seconds.

For the protection of loads such as semiconductor devices or measuring circuits using current transformers.

Circuit breakers are also rated by the maximum fault current that they can interrupt; this allows use of more economical devices on systems unlikely đồ sộ develop the high short-circuit current found on, for example, a large commercial building distribution system.

In the United States, Underwriters Laboratories (UL) certifies equipment ratings, called Series Ratings (or "integrated equipment ratings") for circuit breaker equipment used for buildings. Power circuit breakers and medium- and high-voltage circuit breakers used for industrial or electric power systems are designed and tested đồ sộ ANSI or IEEE standards in the C37 series. For example, standard C37.16 lists preferred frame size current ratings for power circuit breakers in the range of 600 đồ sộ 5000 amperes. Trip current settings dn time-current characteristics of these breakers are generally adjustable.

For medium and high voltage circuit breakers used in switchgear or substations and generating stations, relatively few standard frame sizes are generally manufactured. These circuit breakers are usually controlled by separate protective relay systems, offering adjustable tripping current and time settings as well as allowing for more complex protection schemes.

Types[edit]

Front panel of a 1250 A air circuit breaker manufactured by ABB. This low-voltage power circuit breaker can be withdrawn from its housing for servicing. Trip characteristics are configurable via DIP switches on the front panel.

Many classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features.

Xem thêm: viết đoạn văn nêu tình cảm cảm xúc về cảnh vật quê hương

Low-voltage[edit]

Low-voltage (less kêu ca 1,000 VAC) types are common in domestic, commercial and industrial application, and include:

  • Miniature circuit breaker (MCB)—rated current up đồ sộ 125 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.
  • Molded Case Circuit Breaker (MCCB)—rated current up đồ sộ 1,600 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in larger ratings.
  • Low-voltage power circuit breakers can be mounted in multi-tiers in low-voltage switchboards or switchgear cabinets.

The characteristics of low-voltage circuit breakers are given by international standards such as IEC 947. These circuit breakers are often installed in draw-out enclosures that allow removal and interchange without dismantling the switchgear.

Large low-voltage molded case and power circuit breakers may have electric motor operators ví they can open and close under remote control. These may size part of an automatic transfer switch system for standby power.

Low-voltage circuit breakers are also made for direct-current (DC) applications, such as DC for subway lines. Direct current requires special breakers because the arc is continuous—unlike an AC arc, which tends đồ sộ go out on each half cycle, direct current circuit breaker has blow-out coils that generate a magnetic field that rapidly stretches the arc. Small circuit breakers are either installed directly in equipment, or are arranged in a breaker panel.

Inside a miniature circuit breaker

The DIN rail-mounted thermal-magnetic miniature circuit breaker is the most common style in modern domestic consumer units and commercial electrical distribution boards throughout Europe. The design includes the following components:

  1. Actuator lever - used đồ sộ manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed ví they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred đồ sộ as "free trip" or "positive trip" operation.
  2. Actuator mechanism - forces the contacts together or apart.
  3. Contacts - allow current when touching and break the current when moved apart.
  4. Terminals
  5. Bimetallic strip - separates contacts in response đồ sộ smaller, longer-term overcurrents
  6. Calibration screw - allows the manufacturer đồ sộ precisely adjust the trip current of the device after assembly.
  7. Solenoid - separates contacts rapidly in response đồ sộ high overcurrents
  8. Arc divider/extinguisher

Solid state[edit]

Solid-state circuit breakers, also known as digital circuit breakers are a technological innovation which promises advance circuit breaker technology out of the mechanical level, into the electrical. This promises several advantages, such as cutting the circuit in fractions of microseconds, better monitoring of circuit loads and longer lifetimes.[6]

Magnetic[edit]

Magnetic circuit breakers use a solenoid (electromagnet) whose pulling force increases with the current. Certain designs utilize electromagnetic forces in addition đồ sộ those of the solenoid. The circuit breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch, which lets the contacts open by spring action. They are the most commonly used circuit breakers in the United States.

Thermal-magnetic[edit]

Shihlin Electric MCCB with SHT

Thermal magnetic circuit breakers, which are the type found in most distribution boards in Europe and countries with a similar wiring arrangements, incorporate both techniques with the electromagnet responding instantaneously đồ sộ large surges in current (short circuits) and the bimetallic strip responding đồ sộ less extreme but longer-term over-current conditions. The thermal portion of the circuit breaker provides a time response feature, that trips the circuit breaker sooner for larger over currents but allows smaller overloads đồ sộ persist for a longer time. This allows short current spikes such as are produced when a motor or other non-resistive load is switched on. With very large over-currents during a short circuit, the magnetic element trips the circuit breaker with no intentional additional delay.[7]

Magnetic-hydraulic[edit]

A magnetic-hydraulic circuit breaker uses a solenoid coil đồ sộ provide operating force đồ sộ open the contacts. Magnetic-hydraulic breakers incorporate a hydraulic time delay feature using a viscous fluid. A spring restrains the core until the current exceeds the breaker rating. During an overload, the tốc độ of the solenoid motion is restricted by the fluid. The delay permits brief current surges beyond normal running current for motor starting, energizing equipment, etc. Short-circuit currents provide sufficient solenoid force đồ sộ release the latch regardless of core position thus bypassing the delay feature. Ambient temperature affects the time delay but does not affect the current rating of a magnetic breaker.[8]

Large power circuit breakers, applied in circuits of more kêu ca 1000 volts, may incorporate hydraulic elements in the tương tác operating mechanism. Hydraulic energy may be supplied by a pump, or stored in accumulators. These size a distinct type from oil-filled circuit breakers where oil is the arc extinguishing medium.[9]

Common trip (ganged) breakers[edit]

Three-pole common trip breaker for supplying a three-phase device. This breaker has a 2 A rating.

To provide simultaneous breaking on multiple circuits from a fault on any one, circuit breakers may be made as a ganged assembly. This is a very common requirement for 3 phase systems, where breaking may be either 3 or 4 pole (solid or switched neutral). Some makers make ganging kits đồ sộ allow groups of single phase breakers đồ sộ be interlinked as required.

In the US, where split phase supplies are common, in branch circuits with more kêu ca one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a "common trip" breaker must be used. These may either contain two or three tripping mechanisms within one case, or for small breakers, may externally tie the poles together via their operating handles. Two-pole common trip breakers are common on 120/240-volt systems where 240 volt loads (including major appliances or further distribution boards) span the two live wires. Three-pole common trip breakers are typically used đồ sộ supply three-phase electric power đồ sộ large motors or further distribution boards.

Separate circuit breakers must never be used for live and neutral, because if the neutral is disconnected while the live conductor stays connected, a very dangerous condition arises: the circuit appears de-energized (appliances don't work), but wires remain live and some residual-current devices (RCDs) may not trip if someone touches the live wire (because some RCDs need power đồ sộ trip). This is why only common trip breakers must be used when neutral wire switching is needed.

Shunt-trip units[edit]

A shunt-trip unit appears similar đồ sộ a normal breaker and the moving actuators are 'ganged' đồ sộ a normal breaker mechanism đồ sộ operate together in a similar way, but the shunt trip is a solenoid intended đồ sộ be operated by an external constant voltage signal, rather kêu ca a current, commonly the local mains voltage or   DC. These are often used đồ sộ cut the power when a high risk sự kiện occurs, such as a fire or flood alarm, or another electrical condition, such as over voltage detection. Shunt trips may be a user fitted accessory đồ sộ a standard breaker, or supplied as an integral part of the circuit breaker.

Medium-voltage[edit]

A Siemens air circuit breaker rated for 1000 V and 2500 A continuous current mounted on a motor control cubicle

Medium-voltage circuit breakers rated between 1 and 72 kV may be assembled into metal-enclosed switchgear line ups for indoor use, or may be individual components installed outdoors in a substation. Air-break circuit breakers replaced oil-filled units for indoor applications, but are now themselves being replaced by vacuum circuit breakers (up đồ sộ about 40.5 kV). Like the high voltage circuit breakers described below, these are also operated by current sensing protective relays operated through current transformers. The characteristics of MV breakers are given by international standards such as IEC 62271. Medium-voltage circuit breakers nearly always use separate current sensors and protective relays, instead of relying on built-in thermal or magnetic overcurrent sensors.

Medium-voltage circuit breakers can be classified by the medium used đồ sộ extinguish the arc:

  • Vacuum circuit breakers—With rated current up đồ sộ 6,300 A, and higher for generator circuit breakers application (up đồ sộ 16,000 A & 140 kA). These breakers interrupt the current by creating and extinguishing the arc in a vacuum container - aka "bottle". Long life bellows are designed đồ sộ travel the 6–10 mm the contacts must part. These are generally applied for voltages up đồ sộ about 40,500 V,[10] which corresponds roughly đồ sộ the medium-voltage range of power systems. Vacuum circuit breakers have longer life expectancy between overhaul kêu ca vì thế other circuit breakers. In addition their global warming potential is by far lower kêu ca SF6 circuit breaker.
  • Air circuit breakers—Rated current up đồ sộ 6,300 A and higher for generator circuit breakers. Trip characteristics are often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled via an integral electronic trip unit. Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.
  • SF6 circuit breakers extinguish the arc in a chamber filled with sulfur hexafluoride gas.

Medium-voltage circuit breakers may be connected into the circuit by bolted connections đồ sộ bus bars or wires, especially in outdoor switchyards. Medium-voltage circuit breakers in switchgear line-ups are often built with draw-out construction, allowing breaker removal without disturbing power circuit connections, using a motor-operated or hand-cranked mechanism đồ sộ separate the breaker from its enclosure.

High-voltage[edit]

Three single-phase Soviet/Russian 110-kV oil circuit breakers
400 kV SF6 live-tank circuit breakers

Electrical power transmission networks are protected and controlled by high-voltage breakers. The definition of high voltage varies but in power transmission work is usually thought đồ sộ be 72.5 kV or higher, according đồ sộ a recent definition by the International Electrotechnical Commission (IEC). High-voltage breakers are nearly always solenoid-operated, with current sensing protective relays operated through current transformers. In substations the protective relay scheme can be complex, protecting equipment and buses from various types of overload or ground/earth fault.

High-voltage breakers are broadly classified by the medium used đồ sộ extinguish the arc:

  • Bulk oil
  • Minimum oil
  • Air blast
  • Vacuum
  • SF6
  • CO2

Due đồ sộ environmental and cost concerns over insulating oil spills, most new breakers use SF6 gas đồ sộ quench the arc.

Circuit breakers can be classified as live tank, where the enclosure that contains the breaking mechanism is at line potential, or dead tank with the enclosure at earth potential. High-voltage AC circuit breakers are routinely available with ratings up đồ sộ 765 kV. 1,200 kV breakers were launched by Siemens in November 2011,[11] followed by ABB in April the following year.[12]

High-voltage circuit breakers used on transmission systems may be arranged đồ sộ allow a single pole of a three-phase line đồ sộ trip, instead of tripping all three poles; for some classes of faults this improves the system stability and availability.

High-voltage direct current circuit breakers are still a field of research as of năm ngoái. Such breakers would be useful đồ sộ interconnect HVDC transmission systems.[13]

Sulfur hexafluoride (SF6) high-voltage[edit]

A sulfur hexafluoride circuit breaker uses contacts surrounded by sulfur hexafluoride gas đồ sộ quench the arc. They are most often used for transmission-level voltages and may be incorporated into compact gas-insulated switchgear. In cold climates, supplemental heating or different gas mixtures are used for high voltage circuit breakers, due đồ sộ liquefaction of the SF6 gas. In some northern power grids, gas mixtures of N2 and SF6, or CF4 and SF6 are installed in puffer-type HVCB đồ sộ quench the arc without any liquefaction of the gas. https://ieeexplore.ieee.org/abstract/document/4080767. The minimum temperature ratings of these models are as low as -50 °C for some northern substations.

Disconnecting circuit breaker (DCB)[edit]

The disconnecting circuit breaker (DCB) was introduced in 2000[14] and is a high-voltage circuit breaker modeled after the SF6-breaker. It presents a technical solution where the disconnecting function is integrated in the breaking chamber, eliminating the need for separate disconnectors. This increases the availability, since open-air disconnecting switch main contacts need maintenance every 2–6 years, while modern circuit breakers have maintenance intervals of 15 years. Implementing a DCB solution also reduces the space requirements within the substation, and increases the reliability, due đồ sộ the lack of separate disconnectors.[15][16]

In order đồ sộ further reduce the required space of substation, as well as simplifying the design and engineering of the substation, a fiber optic current sensor (FOCS) can be integrated with the DCB. A 420 kV DCB with integrated FOCS can reduce a substation's footprint with over 50% compared đồ sộ a conventional solution of live tank breakers with disconnectors and current transformers, due đồ sộ reduced material and no additional insulation medium.[17]

Xem thêm: hcl al

Carbon dioxide (CO2) high-voltage[edit]

In 2012, ABB presented a 75 kV high-voltage breaker that uses carbon dioxide as the medium đồ sộ extinguish the arc. The carbon dioxide breaker works on the same principles as an SF6 breaker and can also be produced as a disconnecting circuit breaker. By switching from SF6 đồ sộ CO2, it is possible đồ sộ reduce the CO2 emissions by 10 tons during the product's life cycle.[18]

"Smart" circuit breakers[edit]

Several firms have looked at adding monitoring for appliances via electronics or using a digital circuit breaker đồ sộ monitor the breakers remotely. Utility companies in the United States have been reviewing use of the technology đồ sộ turn on and off appliances, as well as potentially turning off charging of electric cars during periods of high electrical grid load. These devices under research and testing would have wireless capability đồ sộ monitor the electrical usage in a house via a điện thoại thông minh tiện ích or other means.[19]

Other breakers[edit]

Residual current circuit breaker with overcurrent protection

The following types are described in separate articles.

  • Breakers for protections against earth faults too small đồ sộ trip an over-current device:
    • Residual-current device (RCD), or residual-current circuit breaker (RCCB) — detects current imbalance, but does not provide over-current protection. In the United States and Canada, these are called ground fault circuit interrupters (GFCI).
    • Residual-current circuit breaker with overcurrent protection (RCBO) — combines the functions of a RCD and a MCB in one package. In the United States and Canada, these are called GFCI breakers.
    • Earth leakage circuit breaker (ELCB) — This detects current in the earth wire directly rather kêu ca detecting imbalance. They are no longer seen in new installations as they cannot detect any dangerous condition where the current is returning đồ sộ earth by another route - such as via a person on the ground or via plumbing. (also called VOELCB in the UK).
  • Recloser — A type of circuit breaker that closes automatically after a delay. These are used on overhead electric power distribution systems, đồ sộ prevent short duration faults from causing sustained outages.
  • Polyswitch (polyfuse) — A small device commonly described as an automatically resetting fuse rather kêu ca a circuit breaker.

See also[edit]

  • Arc-fault circuit interrupter
  • Breaking capacity
  • Circuit breaker analyzer
  • Circuit total limitation (CTL)
  • Distribution board (Circuit breaker panel)
  • Earthing system
  • Ground Fault Circuit Interrupter (GFCI)
  • Hybrid switchgear module
  • Insulation monitoring device
  • Motor control center (MCC)
  • Network protector
  • Power distribution center (PDC)
  • Power system protection
  • Remote racking system
  • Ring Main Unit
  • Selectivity (circuit breakers)
  • Stab-Lok—a popular type of circuit breaker manufactured from 1950 đồ sộ 1990, now widely deemed unsafe
  • Sulfur hexafluoride circuit breaker
  • Zener diode—a diode that allows current đồ sộ flow in reverse direction (to break at certain level of voltage, an opposite effect)
  • Circuit Breaker

References[edit]

  1. ^ Robert Friedel and Paul Israel, Edison's Electric Light: Biography of an Invention, Rutgers University Press, New Brunswick New Jersey USA,1986 ISBN 0-8135-1118-6 pp.65-66
  2. ^ ""1920-1929 Stotz miniature circuit breaker and domestic appliances", ABB, 2006-01-09, accessed 4 July 2011". Archived from the original on 2013-10-29. Retrieved 2011-07-04.
  3. ^ Flurscheim, Charles H., ed. (1982). "Chapter 1". Power Circuit Breaker Theory and Design (Second ed.). IET. ISBN 0-906048-70-2.
  4. ^ Weedy, B. M. (1972). Electric Power Systems (Second ed.). London: John Wiley and Sons. pp. 428–430. ISBN 0-471-92445-8.
  5. ^ "What is an MCB and how does it work?". Fusebox Shop. 16 September năm 2016. Archived from the original on 11 July 2018. Retrieved 11 July 2018.
  6. ^ "Solid State Circuit Breaker". Archived from the original on 2022-01-25. Retrieved 2018-11-14.
  7. ^ John Matthews Introduction đồ sộ the Design and Analysis of Building Electrical Systems Springer 1993 0442008740 page 86
  8. ^ Hwaiyu Geng, Data Center Handbook, John Wiley & Sons,năm trước page 542
  9. ^ G R Jones (ed), Electrical Engineer's Reference Book, Butterworth - Heinemann Ltd, 1993, page 25/14
  10. ^ A few manufacturers now offer a single-bottle vacuum breaker rated up đồ sộ 72.5 kV and even 145 kV. See https://www.edu-right.com/full-knowledge-about-integrated[permanent dead link] Electrical Engineering in India, vol 157 issue 4 pages 13-23
  11. ^ "Siemens launches world's first 1200kV SF6 Circuit Breaker". Archived from the original on 3 July 2013. Retrieved 14 November 2011.
  12. ^ "ABB đồ sộ develop ultra high voltage circuit breaker". Archived from the original on 4 March 2016. Retrieved 14 August 2012.
  13. ^ "High Voltage DC Switch Enables Supergrids for Renewable Energy, MIT Technology Review". Retrieved 19 July 2013.
  14. ^ "Applications of Disconnecting Circuit Breakers, Michael Faxå, p.1" (PDF). Archived from the original (PDF) on 16 May 2013. Retrieved 9 July 2012.
  15. ^ "HPL Disconnecting Circuit Breaker". Archived from the original on đôi mươi February 2014. Retrieved 9 July 2012.
  16. ^ "Disconnecting Circuit Breakers, Buyer's and Application Guide, p. 10" (PDF). Archived (PDF) from the original on 5 December 2020. Retrieved 15 September 2014.
  17. ^ "362 – 550 kV Disconnecting Circuit Breaker with FOCS: Small, smart and flexible, p.1". Archived from the original on 11 May 2020. Retrieved 3 July 2013.
  18. ^ "Switzerland: ABB breaks new ground with environment friendly high-voltage circuit breaker". Archived from the original on 24 December 2019. Retrieved 7 June 2013.
  19. ^ "Smart circuit-breakers for energy-efficient homes". The Economist. 2017-11-23. Archived from the original on 2018-01-15. Retrieved 2018-01-15.

Sources[edit]

  • BS EN 60898-1. Electrical accessories — Circuit breakers for over-current protection for household and similar installations. British Standards Institution, 2003.